MV Switchgear Panel

Product ratings:
  • 3.6kV, 7.2kV & 12kV up to 1600 Amps, 26.2kA for 3 Sec. Indoor Vacuum Circuit Breaker Panel.
Dimensional Details:
  • 3.6kV, 7.2kV & 12kV : Height (2280mm) width ( 700mm) depth(1800mm)
Features:
  • Full Truck VCB designs Horizontal Draw out.
  • Fully closed door operation of Breaker for Operator safety.
  • With all Electrical & Mechanical safety interlocks as per IEC/IS.
  • Automatic shutters to cover live parts when the circuit breaker or voltage transformer is withdrawn.
  • Pressure release flaps at the top of the panel at safe height. Separate flaps in Circuit Breaker, busbar and cable compartment.
  • Padlocking arrangement for shutters.
  • Standard earthing of cables and busbars through earthing truck.
  • Superior mechanical endurance values. Maintenance required only after 10,000 operations.
Technical Specifications:
  • Type : PMV-700
  • Ref. Standard : IEC 62271-100/200
  • Type tested at NABL Accredited laboratory
  • Rated Power frequency with-stand voltage 28 kV (RMS) at 50 Hz
  • Rated Impulse withstand voltage : 75 kV Peak
  • Operating Method : Manual / Motor Charged Spring
  • Rated operating sequence : 0-3 min.-CO – 3 min.- CO
  • Rated operating sequence for auto reclosing duty : O – 0.3 sec. –CO -3 min. – CO
  • Opening time (approx): 40 mSec.
  • Closing time (approx): 50 mSec.
  • Degree of protection : IP4X
  • Paint Color Shade : Light Grey Shade RAL 7032 (Other colors on request)